Protect Flex Modular Industrial UPS with 10-40 kVA

Protect Flex is based on a new concept of UPS systems that combines a modular architecture based on 10 and 15 kVA/kW hot-swappable power modules with a customizable set of options. The system is an industrial-grade fully modular UPS, flexible and highly cost-effective. It can cope effectively with harsh environmental conditions, with an IP43 rating protection. Protect Flex is designed to maximize savings in terms of footprint and power installed (kVA).

IP43 Protection

Protection against water and dust

Easy Maintenance

Service-friendly design ensures rapid and easy maintenance and minimizes service costs

Industrial-Grade

A robust design crafted for harsh environments and high requirements

Scalability

Parallel operation makes it flexible to adapt the capacity to changing load requirements

Higher Availability

Redundancy capabilities increase the availability of this device to the highest possible level

CAPACITY 10-40 kVA
INPUT PHASES 3 or 1 PH+N+G
INPUT VOLTAGE (L-L) 380/400/415
or 220/230/240
OUTPUT PHASES 3 or 1 PH+N
OUTPUT VOLTAGE (L-L) 380/400/415
or 220/230/240

The Protect Flex of AEG Power Solutions is a new UPS system concept that combines a modular architecture based on 10 and 15 kVA/kW hot swappable power modules, with a large customizable set of options. The system has a robust design which encapsulates AEG Power Solutions’ unmatched expertise for industrial applications. It is suitable for harsh environments and is the only one in its category to be configurable to all electrical system schemes with the benefit of power modularity.

Benefits
Features
Model
Protect Flex Cabinet
Power Module
Maximum capacity (kVA/kW)
20 / 20
30/30
40 / 40
10/10
15/15
Dimensions W x D x H (mm)
600 x 800 x 1810
438 x 590 x 85 (2U)
Weight (kg)
165
165
175
15.3
15.5
Phase configuration
3/3; 3/1; 1/1
3/3
3/3; 3/1; 1/1
3/3; 3/1; 1/1
3/3
Color of the frame
RAL 7035
RAL 7021
Input Phase
3 or 1 Phase + N + G
3 Phase + N + G
3 or 1 Phase + N + G
3 or 1 Phase + N + G
3 Phase + N + G
Nominal Voltage (V)
Ph-N: 220/230/240
Ph-N: 220/230/240
Ph-N: 220/230/240
Ph-N: 220/230/240
Ph-N: 220/230/240
Frequency (Hz)
50 / 60 (with a variable range 40 to 70 Hz)
Input Power Factor
> 0.99
Input THDi
< 3% (with full linear load)
Output Voltage (V)
380 / 400 / 415
Output PF
1
AC/AC efficiency in double conversion
> 95% (at nominal load)
AC/AC efficiency in ECO Mode
> 98% (at nominal load)
Mechanical Options
Functional Options
Communication Options
Inbuilt Isolation Transformer
Protect Plus S500 Download
Call in the experts

We are ready and waiting to offer trusted, expert advice on how to overcome your power challenges and set your organization up for the future. Please get in touch and we will show you what we can do.

Sign up to our newsletter