Specifications
Power Rating Model [kVA] | 250 | 300 | 400 | 500 | 600 |
---|---|---|---|---|---|
Nominal active Power up to 40°C [kW] | 250 | 300 | 400 | 500 | 600 |
Dimensions W x D x H [mm] | 1000 x 900 x 1950 | 1400 x 900 x 1950 | |||
Weight (without batteries/transformer) [kg] | 750 | 1100 | |||
Nominal Voltage (3Ph + N + G) [V] | 380 / 400 / 415 | ||||
Voltage range [V] | 380 VAC (-15% to +25% at full load) 400 VAC (-20% to +20% at full load) 415 VAC (-20% to +15% at full load) | ||||
Frequency [Hz] | 50 / 60 (also settable as frequency converter) | ||||
Input Power Factor | > 0.99 | ||||
Input THDi (at rated voltage and THDv < 0,5%) | < 3% (with full linear load) | ||||
AC/AC efficiency in VFI @ nominal linear load | up to 95.2% | up to 95.4% | up to 95.7% | up to 95.7% | up to 95.7% |
AC/AC efficiency in VFD (Eco Mode) | up to 99% (at nominal load) | ||||
AC/AC efficiency in Smart Eco Mode | up to 98% (at nominal load) | ||||
IP protection degree | IP20 (standard); IP21 & IP31 (optional) | ||||
Color | RAL 9005 |