Model Transokraft 3 N1  Transokraft 3 N1 
rated input dc voltage   220V + 20/-20%  110Vdc  + 20/-20%    
Power rate 30kVA  50kVA  80kVA  120kVA  170kVA  200kVA  20kVA  40kVA  60kVA  80kVA 
rated output AC voltage  400 V (380V – 420 V adjustable) other voltages on reques
Deviation stat.  ±1%
Deviation dyn.  (at load surge   0 – 100 % – 0 without mains support) voltage dip <3%
Frequency without mains synchronization 50Hz ± 0.1%; (60Hz on request)
Power factor range 0 ind. – 1 – 0 cap.
nominal current output per phase 43A  72A 116A 173A 245A 289A 43A  72A 116A 173A
Permissible non-linear load 100%
Cooling system < 3 % in the entire load and DC voltage range also with non-linear load
Overload behaviour/performance 150 % for 1 min. /  125 % for 10 min. 
Short circuit current   4,6 dyn. 6,2 dyn.  5,1 dyn. 6,0 dyn. 6,0 dyn.  4,0 dyn. 4,6 dyn. 5,2 dyn.  6,0 dyn. 6,0 dyn.
Efficieny at 50% nominal load  92% 92% 94% 94.40% 94.40% 94.60% 92% 92% 94% 94.40%